3.3. RS485/RS422 BUS CONNECTION
The RS485/RS422 interface is available in the ADA-13040MG on screw terminal block, labelled as: Tx+/A, Tx-/B, Rx+, Rx-.
The ADA-13040MG allows operating on the RS422 bus and the RS485 bus. Both buses require proper wiring.
3.3.1. CONNECTION TO 4-WIRE RS422 BUS
Before connection 4-wire RS422 bus, should be set the MODE switch on the front panel of ADA-13040MG in RS422 mode. Then
connect wires of bus to terminals TX+/A, TX-/B, RX+, RX-, like below.
Fig. 9. Example connection of the RS422 device to ADA-13040MG
3.3.2. CONNECTION TO 4-WIRE RS485(4W) BUS
Before connection 4-wire RS485 Bus, should be set the MODE switch on the front panel of ADA-13040MG in RS485 mode. Connect
wires of bus to terminals TX+/A, TX-/B, RX+, RX- , like below.
Fig. 10. Example connection of the RS485(4W) devices to ADA-13040MG.
3.3.3. CONNECTION TO 2-WIRE RS485 BUS
Most of the devices with RS485 interface, use 2-wire RS485 bus for data transmission.
Before connection 2-wire RS485 bus, should be set the MODE switch on the front panel of the ADA- 13040MG in RS485 mode.
Connect wires of bus to the terminals TX+/A, TX-/B, like below.
10